Power Generator - 200 KVA (Diesel)
Product code : Brand : tsMachine
Power (kVA) : 3 Phase,50 Hz, PF 0.8 VOLTAGE : 400/231 STANDBY RATING (ESP) : 160 Kw 200 kVA PRIME RATING (PRP) : 145,6 182 Standby Amper : 288,68
Register to the Site Get 3% Discount
By registering on the site, you can see the product prices listed and get a 3% discount.
Power Generator - 200 KVA (Diesel)
Power Generator - 200 KVA (Diesel)
It provides ideal performance in fixed installations, as a backup or continuous power supply.
The high quality standards applied during production prepare the products to be used in a way that does not require service. All tests are done during the manufacture of the generators and before they leave the factory.
Power (kVA) 3 Phase,50 Hz, PF 0.8 | |||||
VOLTAGE | STANDBY RATING (ESP) | PRIME RATING (PRP) | Standby Amper | ||
kW | kVA | kW | kVA | ||
400/231 | 160,00 | 200,00 | 145,60 | 182,00 | 288,68 |
STANDBY RATING (ESP) Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility | |||||
source. ESP is in accordance with ISO 8528-1. Overload is not allowed. | |||||
PRIME RATING (PRP) Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % | |||||
overload capability is available for a period of 1 hour within 12-hour perod of operation. | |||||
General Characteristics |
|||||
Model Name | |||||
Frequency (Hz) 50 | |||||
Fuel Type Diesel | |||||
Engine Made and Model AKSA A6CRX69TI | |||||
Alternator Made and Model AK 4150 | |||||
Control Panel Model DSE 6120 | |||||
Canopy ACP 6B | |||||
ENGINE SPECIFICATIONS |
|||||
Engine AKSA | |||||
Engine Model A6CRX69TI | |||||
Number of Cylinder (L) 6 cylinders - in line | |||||
Bore (mm.) 108 | |||||
Stroke (mm.) 125 | |||||
Displacement (lt.) 6,87 | |||||
Aspiration Turbo Charged and Intercooled(Water to Air) | |||||
Compression Ratio 17:1 | |||||
RPM (d/dk) 1500 | |||||
Oil Capacity (Total With Filter) (lt) 16 | |||||
Standby Power (kW/HP) 182/247.45 | |||||
Prime Power 166/225.7 | |||||
Block Heater QTY 1 | |||||
Block Heater Power (Watt) 1500 | |||||
Fuel Type Diesel | |||||
Injection Type and System Direct | |||||
Type of Fuel Pump P pump | |||||
Governor System Electronic | |||||
Operating Voltage (Vdc) 24 Vdc | |||||
Battery and Capacity (Qty/Ah) 2x80 | |||||
Cooling Method Water Cooled | |||||
Cooling Fan Air Flow (m3/min) 190 | |||||
Coolant Capacity (engine only / with radiator) (lt) 9,35/40 | |||||
Air Filter Dry Type | |||||
Fuel Cons. Prime With %100 Load (lt/hr) 43 | |||||
ALTERNATOR CHARACTERISTICS |
|||||
Manufacturer Aksa | |||||
Alternator Made and Model AK 4150 | |||||
Frequency (Hz) 50 | |||||
Power (kVA) 187.5 | |||||
VOLTAGE (V) 400 | |||||
Phase 3 | |||||
A.V.R. AS460 | |||||
Voltage Regulation (+/-)1,5%% | |||||
Insulation System H | |||||
Protection IP22 | |||||
Rated Power Factor 0.8 | |||||
WEIGHT COMP. GENERATOR (Kg) 580 | |||||
COOLING AIR (m³/min) 30,84 | |||||
Gen.Set Canopy Dimensions (mm) | |||||
LENGTH 3265 | |||||
WIDTH 1163 | |||||
HEIGHT 1858 | |||||
DRY WEIGHT (kg.) 2180 | |||||
TANK CAPACITY (lt.) 271 | |||||
1. Steel structures. | |||||
2. Emergency stop push button. | |||||
3. Control panel is mounted on the baseframe . Located at the right side of the generator set. | |||||
4. Corrosion-resistant locks and hinges. | |||||
5. Oil could be drained via valve and a hose | |||||
6. Exhaust system in the canopy. | |||||
7. Special large access doors for easy maintanance | |||||
8. In front and back side special large access doors for easy maintanance | |||||
9. Base frame -fuel tank. | |||||
11. The cap on the canopy provides easy accsess to radiator cap. | |||||
12. Sound proofing materials | |||||
13. Plastic air intake pockets. | |||||
INTRODUCTION |
|||||
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability. | |||||
Control Panel | |||||
Control Module DSE | |||||
Control Module Model DSE 6120 | |||||
Communication Ports CANBUS | |||||
1. Menu navigation buttons | |||||
2. Close mains button | |||||
3. Main Status and instrumentation display | |||||
4. Alarm LED's | |||||
5. Close generator button | |||||
6. Status LED's | |||||
7. Operation selecting buttons | |||||
Devices | |||||
-DSE, model 6120 Auto Mains Failure control module. | |||||
-Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V) | |||||
-Emergency stop push button and fuses for control circuits. | |||||
CONSTRUCTION and FINISH |
|||||
-Components installed in a sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant surface. Polyester composite powder topcoat forms high gloss and an extremely durable finish. Lockable and hinged panel door provides easy access to components. | |||||
INSTALLATION |
|||||
Control panel is mounted on baseframe with a steel stand. Located at the right side of the generator set (When you look | |||||
at the Gen.Set. from Alternator) | |||||
GENERATING SET CONTROL UNIT |
|||||
The DSE 6120 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts. | |||||
Module monitors the mains supply and switches over to the generator when the mains power fails. | |||||
The DSE6120 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first-up fault condition of Gen. Set failure.The LCD display indicates the fault. | |||||
STANDARD SPECIFICATIONS |
|||||
-Microprocessor controlled. | |||||
-LCD display makes information easy to read. | |||||
-Automatically transfers between mains (utility) and generator power. | |||||
-Manual programming on the front panel. | |||||
-User-friendly set-up and button layout. | |||||
-Remote start. | |||||
-Event logging (50) showing date and time. | |||||
-Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays. | |||||
Instruments | |||||
ENGINE |
|||||
-Engine speed. | |||||
-Oil pressure. | |||||
-Coolant temperature. | |||||
-Run time. | |||||
-Battery volts. | |||||
-Configurable timing. GENERATOR | |||||
-Voltage (L-L, L-N). | |||||
-Current (L1-L2-L3). | |||||
-Frequency. | |||||
-Gen. Set ready. | |||||
-Gen. Set enabled. MAINS | |||||
-Mains ready. | |||||
-Mains enabled. WARNING | |||||
-Charge failure. | |||||
-Battery Low/High voltage. | |||||
-Fail to stop. | |||||
-Low /High generator voltage. | |||||
-Under /Over generator frequency. | |||||
-Over /Under speed. | |||||
-Low oil pressure. | |||||
-High coolant temperature. SHUTDOWNS | |||||
-Fail to start. | |||||
-Emergency stop. | |||||
-Low oil pressure. | |||||
-High coolant temperature. | |||||
-Over /Under speed. | |||||
-Under/over generator frequency. | |||||
-Under/over generator voltage. | |||||
-Oil pressure sensor open. | |||||
-Coolant temperature sensor open. ELECTRICAL TRIP | |||||
-Generator over current. | |||||
Options | |||||
-Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip) | |||||
-Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt). | |||||
Standards | |||||
-Elecrical Safety / EMC compatibility | |||||
-BS EN 60950 Electrical business equipment. | |||||
-BS EN 61000-6-2 EMC immunity standard. | |||||
-BS EN 61000-6-4 EMC emission standard | |||||
STATIC BATTERY CHARGER | |||||
- Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency. | |||||
- Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volts and 27,6 V for 24 V . Input 198 - 264 volt AC. | |||||
- The charger is fitted with a protection diode across the output. | |||||
- Connect charge fail relay coil between the positive output and CF output. | |||||
- They are equipped with RFI filter to reduce electrical noise radiated from the device. | |||||
- Galvanically isolated input and output typically 4kV for high reliability. | |||||
STANDARD SPECIFICATIONS |
|||||
- Heavy duty, water cooled diesel engine | |||||
- Radiator with mechanical fan | |||||
- Protective grille for rotating and hot parts | |||||
- Electric starter and charge alternator | |||||
- Starting battery (with lead acid) including rack and cables | |||||
- Engine coolant heater | |||||
- Steel base frame and anti-vibration isolators | |||||
- Spare external fuel tank (open set) | |||||
- Flexible fuel connection hoses | |||||
- Single bearing, class H alternator | |||||
- Industrial exhaust silencer and steel bellows supplied separately | |||||
- Static battery charger | |||||
- Manual for application and installation | |||||
OPTIONAL EQUIPMENTS |
|||||
ENGINE | |||||
Fuel-Water Seperator Filter | |||||
Low water level alarm | |||||
Oil heater | |||||
ALTERNATOR | |||||
Anti-Condensation Heater | |||||
Main line circuit breaker | |||||
CONTROL SYSTEM | |||||
Earth fault, single set | |||||
Charge Ammeter | |||||
TRANSFER SWITCH | |||||
Three Pole Contactor | |||||
Four Pole Contactor | |||||
Three or four pole motor operated circuit breaker | |||||
OTHER ACCESSORIES |
|||||
Main Fuel Tank | |||||
Automatic or manual fuel filling system | |||||
Manual oil drain pump | |||||
Low and high fuel level alarm | |||||
Enclosure: weater protective or sound attenuated | |||||
Trailer | |||||
Tool kit for maintenance | |||||
CERTIFICATES |
|||||
- TS ISO 8528 | |||||
- TS ISO 9001-2008 | |||||
- CE | |||||
- SZUTEST | |||||
- 2000/14/EC |
Certificates :
You must be a member to add comments/questions.